# How much energy does trimming a pump impeller save?

Canonical: https://senseible.earth/answers/pump-impeller-trimming-energy-saving

If a pump runs against a half-closed valve, trimming the impeller to the flow you need saves energy roughly with the cube of the diameter ratio. A 5% trim cuts power by about 14% on the affinity laws; measure real kW before and after.

## When it fits

- The pump runs at constant flow below its design point.
- A discharge valve is throttled to hold flow.
- Load does not vary much; if it does, a VFD fits better.

## Work it out

1. Measure kW, flow and head.
2. Size the trim with the pump maker's curve.
3. Saving kWh × 0.710 = kg CO2 saved.

## Example: 30 kW pump, 6,000 hours

- 0.95³ = 0.857, so about 14% less power
- 4.3 kW × 6,000 h = 25,800 kWh
- 25,800 × 0.710 = 18.3 t CO2 a year