# Why did my power factor drop and kVAh bill stay high after installing rooftop solar?

Canonical: https://senseible.earth/answers/rooftop-solar-lowers-power-factor-kvah-bill

Solar supplies real power but not reactive power, so the grid still supplies the same reactive load while active import falls. Power factor at the meter drops, and on kVAh billing your units fall less than expected. Retune capacitors or the APFC panel.

## What is happening

Power factor is kW divided by kVA. Solar cuts kW drawn from the grid, but motors still draw kVAr, so the ratio falls.

## Fix

- Re-size the APFC panel for the new import profile.
- Check that the inverter can supply reactive power, if your discom allows it.
- Watch for leading power factor at low load.

## For emissions

Scope 2 uses the kWh imported from the grid, not kVAh. Solar you used yourself carries no grid emissions.