What should our boiler logbook record so the emissions figure holds up?
Fuel fired, not just fuel bought, plus steam produced, operating hours and any fuel test results, every shift or day. Those entries let you reconcile invoices with what was burnt, catch errors before a verifier does, and show efficiency, which is where the cost and CO2 savings come from.
Daily entries
- Fuel fired, by weight or meter reading, per shift.
- Steam generated, from a meter or feedwater reading.
- Operating hours and pressure.
- Fuel type, if more than one is used.
Monthly entries
- Fuel received, opening and closing stock.
- Fuel test reports: calorific value, moisture and ash.
- Blowdown and maintenance notes.
Why it matters
Monthly fuel received should roughly equal fuel fired plus stock change. A gap of more than a few per cent points to weighing errors, losses or misplaced invoices.
What Senseible does here
Senseible reads fuel invoices, gas bills and delivery documents into dated, fingerprinted records, so each tonne of CO2 traces back to the document behind it.
Sources: IPCC 2006 Guidelines, Volume 2 Energy, Bureau of Energy Efficiency, GHG Protocol Corporate Standard
Last reviewed 2026-10-22.