Senseible

How do I estimate the energy and emissions of a laboratory fume hood?

Work out the air the hood exhausts (sash opening area x face velocity), then add the fan power to move it and the cooling energy to condition the replacement air. Multiply the electrical kW by operating hours and by 0.710 kg CO2 per kWh. In a hot, humid climate, cooling the make-up air is usually the biggest part.

Step 1: airflow

Airflow (m3 per second) = open sash area (m2) x face velocity (m per second). Take the sash width, working height and face velocity from the hood's test report. ANSI/ASHRAE 110 describes how hoods are tested for containment; the design face velocity is set by your safety team or the HVAC design, not by that standard.

Step 2: conditioning the replacement air

All exhausted air is replaced by outdoor air that must be cooled and dried. Thermal load (kW) = airflow x 1.2 kg per m3 x enthalpy drop (kJ per kg). Divide by the chiller plant's COP to get electrical kW. Use an annual average enthalpy drop for your city from the HVAC designer, not the peak design day.

Step 3: fans and hours

Fan power (kW) = airflow x total pressure (Pa) / fan efficiency / 1,000, for both exhaust and supply fans. Multiply the total electrical kW by hours of operation. Many hoods run 24 hours a day; check the BMS.

What changes the answer most

Worked example: one VAV hood in a humid city

Face velocity, enthalpy drop, COP, pressure, fan efficiency and 24 hour running are assumptions; take real values from your HVAC design and BMS. Hood energy is already inside your electricity bill, so do not add it to Scope 2.

What Senseible does here

Senseible reports the building's electricity and DG emissions from your bills, at the CEA factor of 0.710 kg CO2 per kWh, CO2 Baseline Database version 21.0, and keeps each bill as evidence for the totals your hood estimates sit within.

Sources: CEA CO2 Baseline Database, GHG Protocol Corporate Accounting and Reporting Standard

Last reviewed 2026-10-18. Comparisons such as one hood equals a number of homes are based on US data and are left out on purpose.