What air ratio or flue gas oxygen should my furnace or boiler run at?

Air ratio is 21 divided by (21 minus the percent oxygen in flue gas). BEE's MSME guidelines target 1.15 to 1.20 for oil-fired and 1.12 to 1.15 for gas-fired furnaces. For boilers the targets are 1.32 to 1.38 on coal and 1.32 to 1.39 on biomass, with carbon monoxide kept within 200 ppm.

Furnace targets

Boilers, thermic fluid heaters and hot air generators

Turning it into an oxygen reading

Rearranged, oxygen % = 21 minus 21 divided by the air ratio. An air ratio of 1.15 is about 2.7% oxygen, 1.20 is 3.5% and 1.38 is about 5.8%. Read oxygen and carbon monoxide together: low oxygen with carbon monoxide above 200 ppm means too little air.

How to hold the target

What Senseible does here

Senseible turns fuel invoices into monthly fuel use and emissions, so a combustion tune-up shows up as less fuel for the same output.

Sources: BEE, Energy Conservation Guidelines for MSME Sector (2019): Tables 6.8, 6.22, 6.39, 6.66 and 6.71, with the air ratio formula