Does a harmonic filter save electricity in a factory with many drives?
A little, mostly by cutting heating losses in cables and transformers. The bigger gains are fewer drive trips, longer capacitor life and a steadier power factor. Measure total harmonic distortion and kWh before and after; do not assume a saving figure.
Where losses come from
Harmonic currents add to RMS current, which heats cables and transformers. Removing them lowers those losses, usually a small share of total consumption.
How to test
- Log THD and kWh at the main incomer for a typical week.
- Install the filter and log again under the same production.
- Count only the measured change, multiplied by 0.710 kg CO2 per kWh for Indian grid power.