When should an old cold store be re-piped, and how much power does pressure drop cost?

Re-pipe if the store was built before 2005 or loses more than 0.2 bar between evaporator and condenser, says TERI's Kundli profile. Each 0.1 bar of drop costs almost 2 C of suction and about 7% more power. New pipe, insulation and valves cut electricity 5 to 8%, paid back within a year.

How to measure the drop

  1. Fit two identical, calibrated pressure gauges: one at the compressor, one at the evaporator.
  2. Read both at steady load and note the difference.
  3. Walk the pipe run with a checklist: frost on pipes or valves means the insulation has failed.
  4. Look hard at corroded lines; Kundli stores use mild steel pipe for ammonia, typically 250 to 400 feet of it.

What the profile found in Kundli

Other fixes from the same study

Building the case for a lender

Keep twelve months of power bills, tonnes in store each month and the two gauge readings. After the work, take the same readings in the same season. The kWh difference against tonnes stored is the figure a bank or buyer will trust.

A 3,710 t store (estimate)

Store sizes and kWh from TERI's Kundli profile (2014-15); the 0.1 bar rule is the profile's rule of thumb. Grid factor from CEA for FY 2025-26.