Do AC and refrigeration equipment makers report refrigerant leakage during customers' use, and how?

Yes. Refrigerant that leaks from ACs and refrigeration units while customers use them is a direct use-phase emission, so the maker reports it in Scope 3 Category 11. Estimate it as units sold x refrigerant charge x annual leak rate x lifetime years x the gas's GWP, in kg CO2e.

Where each refrigerant release goes in the maker's inventory

The inputs and where to get them

Rules that trip makers up

What to disclose

State the charge, leak rate, lifetime and GWP used for each product family, and whether the leak rate is from your field data or an IPCC default. Show refrigerant and electricity as two lines, because buyers and investors compare them when you switch to a lower GWP gas or a more efficient compressor.

Worked example: 10,000 split ACs on R-32 sold in India (assumptions labelled)

Charge, leak rate, running hours and life are illustrative. Use your nameplate data and field service records.

What Senseible does here

For your own sites, Senseible reads electricity bills and fuel slips and keeps the refrigerant purchase invoices you upload as evidence. The use-phase estimate for products you sell is built from your sales and product data, as in the example above.

Sources: GHG Protocol Technical Guidance for Calculating Scope 3 Emissions (2013), Categories 11 and 12, IPCC AR6 WG1, Chapter 7 Supplementary Material, Table 7.SM.7 (GWP-100 values), 2006 IPCC Guidelines, Volume 3, Chapter 7 (refrigeration and air conditioning emission factors)

Last reviewed 2026-10-17. Leak rates are IPCC default ranges and GWPs are AR6 values; confirm the GWP set your buyers ask for.