Our 11 kilovolt (kV) switchgear has never needed a gas top-up. Do we report zero sulphur hexafluoride (SF6) loss, or use an Intergovernmental Panel on Climate Change (IPCC) default?

No. The IPCC 2006 Guidelines define sealed-pressure equipment as needing no top-up for its whole life, so refill records show nothing though gas escapes slowly. Table 8.2 gives use factors of 0.002 (Europe) and 0.007 (Japan) of nameplate charge a year. The Japan figure covers all equipment types, so state which you used.

Two kinds of SF6 equipment

Volume 3 Chapter 8 splits SF6 equipment in two. Sealed-pressure systems are "equipment that does not require any refilling (topping up) with gas during its lifetime" and generally hold less than 5 kilograms of gas per functional unit; "Distribution equipment normally falls into this category." Closed-pressure systems need refilling during their life, generally hold between 5 and several hundred kilograms per unit, and transmission equipment normally falls here.

Our reading: gas-insulated 11 kV and 33 kV panels in a factory yard are distribution equipment, so most are sealed pressure. Check the nameplate or the maker's data sheet for the type.

Why refill records show nothing

The mass balance for use, Equation 8.6A, is the SF6 used to recharge closed-pressure equipment at servicing minus the SF6 recovered. A sealed panel is never recharged, so that sum is zero by design. The Guidelines say the emission-factor approach "is likely to be more accurate for sealed-pressure equipment everywhere", and that the pure mass-balance approach is likely to be appropriate for countries where emissions from sealed-pressure systems are likely to be negligible. Zero on the refill sheet is not evidence of zero loss.

The Tier 1 defaults in Table 8.2

How this sits with our switchgear leak page

That page shows a 0.5 percent a year screening rate taken from a data sheet and puts refill records first. For sealed panels, use the data sheet rate only if the maker states it, and otherwise use one of the two IPCC values above. 0.005 (0.5 percent) sits between 0.002 (0.2 percent) and 0.007 (0.7 percent). If a service report does show refills for a panel, it is closed pressure by the Guidelines' definition, and the refill kilograms are the better measure, as that page explains.

Six sealed panels, 24 kilograms of SF6 on the nameplates

The 24 kilograms is an example total, 4 kilograms a panel, under the Guidelines' 5 kilogram sealed-pressure guide; read your own nameplates. State the region you picked and the year of the table.