How much electricity does a VFD on boiler FD and ID fans save in a small textile unit?

About a quarter of the fan's power, if the fan is big and throttled. BEE's Solapur report fits a drive to an ID fan drawing 9.16 kW with its damper 30 to 40% open: 8,250 kWh saved a year, Rs 0.20 lakh at Rs 2.42 a kWh. Cost Rs 0.32 lakh, payback 1.6 years, not the cover's 1.9.

Why a damper wastes power

About 30 boilers and 10 thermic fluid heaters in the cluster have ID fans pulling flue gas and FD fans pushing combustion air, controlled by hand-set dampers. A fan with its damper half shut still spins at full speed. Fan power falls with the cube of speed, so slowing the motor instead of choking the air cuts power far more than the flow. The report assumes 25%, a little under the cube law's 27% for a 10% slower fan.

Two fans, two answers

What it costs and how to fit it

The fuel is a separate question

These boilers burn wood and other biomass. The drive saves only electricity. Good draught control can also trim excess air and fuel, but the report does not count that. Wood CO2 is biogenic and is reported apart from fossil emissions.

The 9.16 kW ID fan, one year

CO2 at CEA's FY 2025-26 grid factor of 0.675 kg per kWh.

What Senseible does here

Senseible's calculators turn kWh into CO2 on the current grid factor, and it reads monthly electricity bills into records with the bill attached. It has no factor for wood, so keep the tonnes burnt in your own log.

Sources: BEE, Detailed project report: variable frequency drives for FD and ID fans, Solapur textile cluster (SAMEEEKSHA), CEA CO2 Baseline Database, version 22.0