What efficiency should an industrial centrifugal fan or blower reach?
BEE gives peak efficiency ranges by fan type: 79 to 83% for airfoil, backward curved or inclined blades, 72 to 79% for modified radial, 69 to 75% for radial, 58 to 68% for pressure blowers and 60 to 65% for forward curved. Measure your fan's flow, pressure and shaft power and compare.
Peak efficiency by type
- Airfoil, backward curved or inclined: 79 to 83%
- Modified radial: 72 to 79%
- Radial: 69 to 75%
- Pressure blower: 58 to 68%
- Forward curved: 60 to 65%
How to measure your fan
- Measure average velocity pressure across the duct with a pitot tube and inclined manometer, in mm water column.
- Velocity (m/s) = Cp x square root of (2 x 9.81 x velocity pressure / gas density). Use the pitot maker's Cp, or 0.85.
- Flow (m3/s) = velocity x duct area.
- Shaft power (kW) = electrical input (kW) x motor efficiency.
- Static efficiency (%) = flow x static pressure (mm WC) / (102 x shaft kW) x 100. Use total pressure for mechanical efficiency.
Usual fixes when a fan is low
- Fit a VFD where flow varies, instead of throttling with a damper.
- Replace an oversized fan with one sized for the real load.
- Keep the suction clean and clear, and plug duct leaks.
- Replace rewound motors with IE3 motors.
Example: a backward curved process fan (illustrative)
- Flow 10 m3/s, static pressure 150 mm WC
- Electrical input 25 kW, motor efficiency 92%: shaft power 23.0 kW
- Static efficiency = 10 x 150 / (102 x 23.0) x 100 = 63.9%
- That is well below the 79 to 83% peak for this fan type, so look at dampers, sizing and leaks
Readings are illustrative.