How much power can a tile plant save in its slip agitation section?

BEE's Morbi report gives three options on a section using 350,989 kWh a year. A timer that runs agitators 40 minutes an hour saves 105,297 kWh for Rs 0.22 lakh. VFDs save 52,648 kWh for Rs 3.99 lakh, payback 1.87 years. Efficient motors save 14,529 kWh, payback 3.4 years.

Why agitators waste power

Agitators keep ground slip uniform in the underground tanks until it goes to the spray dryer, and they run 24 hours a day. Motor load is 65 to 72% just after fresh slip arrives from the ball mill, then drops once the mix is even. BEE measured seven 5.5 kW agitator motors at 21 to 55% load, and the lightly loaded ones ran at 35 to 53% efficiency.

The three options side by side

Check this before you choose

One tile plant, one year (estimate)

CO2 at CEA's FY 2025-26 grid factor of 0.675 kg per kWh. Money at the report's Rs 4.05 a kWh.