What does a desuperheater on a 210 tonne of refrigeration dairy plant save compared with a 100 tonne one, and why does the payback improve?

A desuperheater, a heat exchanger that turns the hot gas leaving a dairy's ammonia compressors into hot water, saves 38,410 kilograms of furnace oil a year on a 210 tonne of refrigeration (TR) plant and 19,047 on a 100 TR plant in the Bureau of Energy Efficiency (BEE) Gujarat reports. The saving doubles; the cost does not.

What a desuperheater does, in plain words

A dairy's refrigeration does not make cold from nothing. It pumps heat out of the milk, and the compressors push that heat out as very hot gas, which is normally thrown away. Think of the warm back of a household fridge. A desuperheater is a heat exchanger on the compressor's outlet pipe that catches part of that heat in water, so the oil-fired boiler has less water to heat for cleaning in place (CIP) and boiler feed.

The two reports side by side

Why the payback improves

In plain words, both plants catch the same share of their heat, so the saving grows with the load. Our reading: the saving works out to 14% of the heat absorbed from the milk (72.9 TR x 3,024 kilocalories x 14% and 147 TR x 3,024 x 14%). That is 10% of the heat rejected at the condenser, which the report also prints (30,863 of 308,630 kilocalories an hour). The reports themselves call it 10 to 14%. So the saving is in step with the load: 19,047 / 72.9 = 261 kilograms of oil for each TR on load, and 38,410 / 147 = 261 as well.

The cost is not in step. It is Rs 0.285 lakh for each TR on load in the small plant and Rs 0.220 lakh in the large one, because piping, tank and controls are partly fixed. Our own arithmetic, from the printed figures.

The share of the plant's oil is different. The 100 TR chilling centre burns 105,972 kilograms a year, so 19,047 is 18%. The 210 TR dairy burns 442,020 kilograms, so 38,410 is 8.7%. A big saving in tonnes can still be a small cut in the oil bill.

Two things to check in the 210 TR report

Before you fit one

  1. Check you can use about 37,000 litres of 60 degree water a day. Heat with nowhere to go saves nothing.
  2. Read the compressor's discharge temperature and on-load TR from the plant log, not the nameplate. The saving moves with the load.
  3. Check what fuel makes your hot water now. If it is gas or wood, redo the money and the CO2 with that fuel.

Both plants, line by line

These are the reports' printed figures with simple arithmetic on top. The CO2 line is our reading at a different oil factor from the report's, not a figure the report prints. Prices are the reports' 2010 prices.

What Senseible does here

Senseible reads fuel invoices and electricity bills into monthly records, so the fall in furnace oil after fitting shows up against the small rise in power. Water metering can be added as a custom service, on request. Meanwhile keep a water meter reading or tank log beside the bills.

Sources: BEE and SAMEEEKSHA detailed project report: waste heat recovery by desuperheater, 210 TR, Gujarat dairy cluster, BEE and SAMEEEKSHA detailed project report: waste heat recovery by desuperheater, 100 TR, Gujarat dairy cluster, IPCC 2006 Guidelines, Volume 2 Energy, Table 1.2 (net calorific values) and Chapter 2 tables, CEA CO2 Baseline Database for the Indian Power Sector, version 22.0 (FY 2025-26 grid factor)

Last reviewed 2026-11-07. Costs and paybacks are at the reports' 2010 prices. The per-TR figures and the CO2 reading at 3.13 are our own arithmetic on the printed numbers; recheck with today's oil price and a current quote.