Does a vapour absorption chiller run on waste heat cut emissions compared with an electric chiller?

Yes, when the heat is genuine waste that would otherwise be lost: you save most of the electric chiller's kWh and pay only for pumps and a bigger cooling tower. If a boiler burns fuel to make that heat, a good electric chiller usually emits less: absorption gives only 0.7 to 1.2 units of cooling per unit of heat.

Why the heat source decides everything

An electric chiller at 0.65 kW per TR delivers about 5.4 units of cooling per unit of electricity (3.517 / 0.65). A vapour absorption machine (VAM) delivers about 0.65 to 0.7 units of cooling per unit of heat in a single effect machine and about 1.2 in a double effect one, which needs higher grade heat (CIBSE Datasheet 7, absorption cooling). That trade only pays in CO2 when the heat costs no extra fuel: DG or gas engine jacket water and exhaust, excess low pressure steam, hot condensate or process waste heat.

The test for genuine waste heat

Costs people forget

How to report the change

Electricity avoided lowers location-based Scope 2 at 0.710 kg CO2 per kWh. Any fuel burned for the VAM is Scope 1. Report both lines rather than a single net saving, so a reviewer can see the heat source assumption.

Illustrative example: 200 TR for 5,000 hours (1,000,000 TR hours)

kW per TR, COP and boiler efficiency are assumptions; use your data sheets and measured hours.

What Senseible does here

Senseible reads electricity and fuel bills into one monthly record, so the shift from chiller kWh to heat, and any extra fuel, shows on the same page.

Sources: GHG Protocol Corporate Standard, 2006 IPCC Guidelines, Volume 2 Energy (residual fuel oil default), CEA CO2 Baseline Database, version 21.0