What harmonic distortion limits should my factory meet at the supply point?

BEE's MSME guidelines adopt IEEE 519-1992 limits at the point of common coupling: total voltage distortion of 8%, with 5% for any single harmonic, at 1 kV and below, and 5% total with 3% individual from 1 kV to 69 kV. Current limits depend on the ratio of short circuit current to load current.

Voltage distortion limits

Current distortion limits

Where and how often to measure

Measure at the point of common coupling, which BEE places between the plant and the supply network and between non-linear loads and other loads. Log voltage and current THD with a power analyser every month and check that filters are working.

Ways to bring distortion down

Check your own supply terms

Your discom's supply code or connection agreement may set its own limits. Use those where they differ.

What Senseible does here

Senseible works from bills, so it sees the effect of harmonics only through units and power factor. Distortion itself needs a power analyser at the incomer.

Sources: BEE, Energy Conservation Guidelines for MSME Sector (2019): section 5.9, Tables 5.18 and 5.19 (from IEEE 519-1992)

Last reviewed 2026-10-24.