Senseible

How should a Johor data centre report Scope 2 emissions for its customers?

Report a location-based figure using Malaysia's published grid emission factor and a market-based figure using any green electricity tariff, power purchase agreement or certificates retired for the site, then allocate to customers by their metered IT energy. Name each factor and its year.

Location based

Multiply total facility electricity by the grid emission factor published for Peninsular Malaysia for the reporting year. Use the official figure and cite it; do not borrow another country's factor.

Market based

Customer allocation

Allocate facility emissions by each customer's metered IT energy, so cooling and losses follow load through PUE. Give each customer both figures and the contract evidence behind the market-based one.

What Senseible does here

Senseible reads electricity bills and generator fuel invoices into a dated, fingerprinted Scope 1 and 2 record per site. Grid factors outside India must be entered from the official source for the country and year, and are labelled with that source.

Sources: GHG Protocol Scope 2 Guidance, GHG Protocol Corporate Standard

Last reviewed 2026-10-21.