How does a customer count its share of a Johor data centre's emissions?

A colocation customer reports its share in Scope 3, category 1 (purchased goods and services), unless it controls the space's energy contract. The fair key is the customer's metered IT energy times the site's PUE, then times the operator's emission factor for the period.

Steps

Get your metered IT energy for the period from the operator.

Multiply by the site PUE for the same period.

Multiply by the operator's electricity emission factor, location-based and market-based if both are given.

When it is Scope 2

If you buy the electricity for your cage directly, or control it under the lease, it is your Scope 2. Check the contract, not the invoice layout.