The Bureau of Energy Efficiency report for Punjab foundries puts a variable frequency drive on a 22 kilowatt screw compressor: why do its loading and unloading hours look swapped?

The Bureau of Energy Efficiency (BEE) report counts 9,375 kilowatt hours (kWh) saved a year for rupees (Rs) 1.00 lakh, a payback of 2.13 years. Its savings sum is right at 7.5 kilowatts for 5 hours a day over 250 days. Its annexure labels the 1,260 unloaded hours as loading hours.

What a variable frequency drive does to an idling compressor

A screw compressor fills the air tank, and when the tank is full it keeps spinning without making air. That is called running unloaded. It is like leaving a car idling at a red light with the engine still burning fuel. A variable frequency drive (VFD) is a speed controller. It slows the motor to match the air you use, so it does not idle.

The report fits one to a 140 cubic feet a minute compressor with a 22 kilowatt motor. The motor draws 22 kilowatts when loaded and 7.5 when unloaded.

The figures as printed

Where the report's own labels disagree

What the saving assumes

The report says the drive would completely avoid the unloading time, so it counts the whole 7.5 kilowatts as saved. That is how the report words it. My reading, not the report's: a compressor on a drive still draws some power at its lowest speed, so ask the maker for that figure before you take the saving as given.

On the corrected hours (2,340 loaded, 1,260 unloaded) the compressor uses about 22 x 2,340 + 7.5 x 1,260 = 60,930 kWh a year, so 9,375 kWh is about 15% of its electricity. That is arithmetic on the report's figures, not something the report states.

Example: your own compressor, same method

The 70% is an example for a drive that does not bring the idle draw to zero. The report itself assumes the whole unloaded draw is saved. Read your hours off the compressor controller.

What Senseible does here

Senseible reads fuel invoices and electricity bills into monthly records, so the plant's units are on file before and after a drive goes in. The standard product reads bills; compressor meters or hour counters can be added on request.

Sources: BEE, Detailed project report: variable frequency drive on a screw compressor, Batala, Jalandhar and Ludhiana foundry cluster (SAMEEEKSHA)

Last reviewed 2026-11-07. Report figures are from BEE's Small and Medium Enterprises (SME) programme, at its Rs 5 a unit tariff and an implied grid factor of about 0.81 kilograms a kWh (7.6 tonnes over 9,375 kWh), which is older than today's. Check your tariff and a current drive quote before you rely on the payback.