What is CUE and how is it different from reporting data centre Scope 2?

CUE, carbon usage effectiveness, is the CO2 from all energy a data centre uses divided by its IT equipment energy, in kg CO2 per IT kWh. Scope 2 is an absolute total of purchased electricity emissions only. CUE is a ratio, includes diesel generators, and is for tracking efficiency, not for your inventory.

The formula

CUE = total CO2 from data centre energy / IT equipment energy in kWh. Total CO2 covers grid electricity and on-site generation such as diesel sets. For a site that runs only on grid power, CUE equals PUE x the grid factor, so with grid power alone it moves with both cooling efficiency and the grid's carbon intensity.

Four ways it differs from Scope 2

Location-based or market-based

CUE can be computed with either grid factor. State which. In India the location-based figure uses the CEA weighted average; a market-based figure needs certificates or a green tariff with matching units. Do not mix them across years or sites.

For colocation customers

Your provider's CUE describes their whole site. Your own emissions come from your metered IT kWh x their PUE x the grid factor, and whether that sits in your Scope 2 or Scope 3 depends on who buys the electricity. Ask for the provider's CUE basis and period before quoting it.

Illustrative example: one year with a diesel backup set

Figures are illustrative. Factors: CEA CO2 Baseline Database version 21.0 and the IPCC 2006 diesel default.

What Senseible does here

Senseible reads electricity bills (billing period, tariff category, sanctioned load, units) and applies the CEA grid factor of 0.710 kg CO2 per kWh, CO2 Baseline Database version 21.0, for location-based Scope 2, and reads diesel invoices at 2.68 kg CO2 per litre for Scope 1.

Sources: ISO/IEC 30134-8, Data centres key performance indicators, Part 8: Carbon usage effectiveness (iso.org), GHG Protocol Scope 2 Guidance, CEA CO2 Baseline Database

Last reviewed 2026-10-18. Check the current edition of ISO/IEC 30134-8 before citing it in a report.