How do I calculate the electricity and CO2 saved by an LED lighting retrofit in a factory or warehouse?

kWh saved = (old fitting watts including ballast minus new LED watts) x number of fittings x burning hours a year / 1,000. Multiply kWh saved by 0.710 kg CO2 per kWh for location-based Scope 2 and by your tariff for rupees. Measure the old system watts, not just the lamp rating.

Get the old wattage right

Metal halide, sodium vapour and old tube lights draw more than the lamp rating because the ballast or choke uses power too. Measure one fitting of each type with a clamp meter, or add the ballast loss from the maker's data. Using lamp watts alone understates the saving.

Burning hours

Use actual hours per day and days per year for each area, not the factory's working hours. Stores, corridors and yard lights often run longer than production halls. If you add occupancy sensors or daylight controls at the same time, count the hours reduction separately so each measure can be checked.

Checking the saving afterwards

Lighting is usually a small share of a factory bill, so the whole-factory units will not show the saving clearly. The retrofit isolation approach in IPMVP fits better: measure the wattage of old and new fittings once, log hours on a sample, and calculate. A lighting sub-meter, if you have one, gives the before and after directly.

Side effects to count

Worked example: warehouse high bays

What Senseible does here

Senseible reads the units on your electricity bills and applies the CEA factor of 0.710 kg CO2 per kWh, so before and after periods can be compared from documents. The fitting count, wattages and saving claim stay your own records.

Sources: BEE Guide Book 3, Energy Efficiency in Electrical Utilities, Lighting System chapter (beeindia.gov.in), CEA CO2 Baseline Database, version 21.0

Last reviewed 2026-10-18.