Can a voltage stabiliser cut a rice mill's electricity use?

It protects motors on a weak supply, but do not bank on the kWh. BEE's Ganjam report claims 9,503 kWh a year from a 75 kVA stabiliser on a 2 TPH mill, Rs 0.40 lakh, payback 2.63 years. That figure treats the whole load as a loss. Meter the mill with and without it before you count any saving.

The problem is real

Ganjam mills draw power through shared distribution transformers that are smaller than the load. BEE measured 270 to 350 volts against 415 needed, and about 30% of mills face acute low voltage. Motors pull more current, windings overheat and burn, and owners run only part of the line, so motors sit lightly loaded. A stabiliser holds the output at 415 volts within 1%.

What the report claims

Why the kWh figure does not hold

When it is still worth buying

  1. Count the motors rewound in the last two years and their cost. Fewer burnouts is the solid return.
  2. Ask the discom about a dedicated or larger transformer; it fixes the cause.
  3. If you fit a stabiliser, log kWh per tonne for a month with it bypassed and a month in service, at similar output.

What the claim would be worth if it held

CO2 at CEA's FY 2025-26 grid factor of 0.675 kg per kWh. Shown only to correct the report's figure, not as an expected saving.