Senseible

Do voltage optimisers or servo stabilisers really cut electricity and emissions?

Only for loads that use less power at lower voltage, such as some lighting and resistive heaters. Motors on drives, LED drivers and electronics often save little. A stabiliser also has its own losses. Measure kWh with the unit bypassed and in service before counting any saving.

Loads that may respond

Loads that usually do not

How to test

Alternate weeks with the unit in service and bypassed at similar production, and compare kWh per unit made. Count only a measured saving, multiplied by 0.710.

What Senseible does here

Senseible reads fuel invoices and electricity bills and applies IPCC 2006 factors and the CEA grid factor (0.710 kg CO2 per kWh), so you can compare Scope 1 and 2 before and after a change from the documents themselves.

Sources: CEA CO2 Baseline Database for the Indian Power Sector, Bureau of Energy Efficiency, GHG Protocol Scope 2 Guidance

Last reviewed 2026-10-22.