Do voltage optimisers or servo stabilisers really cut electricity and emissions?
Only for loads that use less power at lower voltage, such as some lighting and resistive heaters. Motors on drives, LED drivers and electronics often save little. A stabiliser also has its own losses. Measure kWh with the unit bypassed and in service before counting any saving.
Loads that may respond
- Older lighting and resistive heating.
- Lightly loaded motors without drives, sometimes.
Loads that usually do not
- Motors on variable speed drives.
- LED drivers and electronics with regulated supplies.
- Heaters on thermostats, which simply run longer.
How to test
Alternate weeks with the unit in service and bypassed at similar production, and compare kWh per unit made. Count only a measured saving, multiplied by 0.710.