How many earth pits and what earth resistance does a rooftop solar plant need under the Ministry of New and Renewable Energy specification?

The Ministry of New and Renewable Energy (MNRE) specification says earth resistance shall never be higher than 5 ohms. For systems of 10 kilowatts and above it asks for three separate earth pits, one each for direct current side earthing, alternating current side earthing and the lightning arrestor.

Earthing, clause 8.1

These are clauses from the technical specification in Annexure 3 of MNRE's guidelines for its residential rooftop solar scheme, Pradhan Mantri Surya Ghar: Muft Bijli Yojana. A factory is not bound by them, but they are a published checklist to hold a quotation against.

Lightning and surge protection

Points to put in the quotation

Pit count by plant size (reading clause 8.1.5)

Plant sizes and readings are examples. The 5 ohm limit and the 10 kW line are MNRE's.

What Senseible does here

Senseible reads fuel invoices and electricity bills into monthly records. It does not check earthing, protection or any site safety item.

Sources: Ministry of New and Renewable Energy (MNRE), Guidelines for PM-Surya Ghar: Muft Bijli Yojana, Central Financial Assistance to Residential Consumers, with Annexures 2 to 4

Last reviewed 2026-11-06. Re-check clause numbers and figures against the current version of the guidelines before you rely on them. Clause numbers are from Annexure 3, sections 7 and 8. A safety design is for a qualified electrical engineer to approve.