What minimum specification should a rooftop solar inverter meet on overload, harmonics, power factor and losses?

The Ministry of New and Renewable Energy (MNRE) specification asks for an inverter with at least 20% overloading capacity, no-load losses under 1% of rated power, harmonic distortion under 3%, power factor above 0.9 lag or lead, and direct current (DC) injection no more than 0.5% of full rated output.

The numbers in clauses 2.6 and 2.7

These are clauses from the technical specification in Annexure 3 of MNRE's guidelines for its residential rooftop solar scheme, Pradhan Mantri Surya Ghar: Muft Bijli Yojana. A factory is not bound by them, but they are a published checklist to hold a quotation against.

Build and data features

Where it ties to your bill

My reading: a power factor above 0.9 is a floor for the inverter, not a cure for your plant's reactive load. If your bill is on kilovolt-ampere hour (kVAh) units and the power factor drops after solar, see the page on that effect. Check the Quality Control Order for solar inverters (clause 2.1 names the one dated 30.08.2017) and the page on inverters above 200 kilowatts for the current certification route.

Reading the limits for a 50 kW inverter (example size)

The 50 kW size is an example. The percentages are MNRE's.

What Senseible does here

Senseible reads electricity bills into monthly records, so the units you import month by month sit in one place. Inverter data is a custom integration on request. It does not check an inverter against a standard.

Sources: Ministry of New and Renewable Energy (MNRE), Guidelines for PM-Surya Ghar: Muft Bijli Yojana, Central Financial Assistance to Residential Consumers, with Annexures 2 to 4

Last reviewed 2026-11-06. Re-check clause numbers and figures against the current version of the guidelines before you rely on them. The specification text is in Annexure 3, section 2. Inverter certification rules change, so check the current order.